No products in the Quote.
Home Our Equipment Water Quality Monitors ORAKEL
The ORAKEL System is ideal for all your water monitoring equipment needs, measuring both water flow and water quality at the same time. Created as a modular system, a wide range of water quality sensors can be added to measure various characteristics, such as pH, COD and suspended solids, for a truly bespoke and cost-effective solution.
Two sensors can be connected as standard to one controller. However, one configured system could have up to 16 sensors connected and controlled by one controller. The ORKAEL system’s range of water monitoring equipment includes three flow meters and five different pH meters. It has a range of conductivity and TDS meters for different applications and many other sensors. All the sensors are compatible and both flow meter and water quality sensors can be configured onto one system.
Optional comms packages allow Profibus, Modbus ASCII, Modbus RTU, Modbus TCP, 4-20mA analogue outputs and relays for alarms and control.
The ORAKEL controller is equipped with a display screen, readings can be taken directly from the control unit or downloaded from the internal data logger. An optional Detectronic modem allows for remote communication capabilities.
PID Control
Full PID control suitable for nearly all dosing requirements, from simple to very complex processes.
Diagnostics
Includes a full set of instrument and measurement diagnostics.
Precision Positioning
An integrated signal oscilloscope optimises sensor positioning and diagnostics.
Easy Configuration
Includes a comprehensive internal database of pipe, fluid and lining materials.
Built-in Parameters
Built-in fluid parameters allow calculation to compensate for sound speed, density, viscosity, specific heat capacity and temperature (if temperature is known from optional temperature probe).
Flexible Measurement
Liquid can be measured in M, m3, USgal, mg, cf, bbl and Imp bbl. All measured values can be selected as flow rate per second, minute, hour or day and are automatically totalised.
Data Analysis
An optional GSM data-logger can be added and date sent to an online portal for detailed analysis.
The ORAKEL System is suitable for use in closed, partially filled and open channels.
The wide variety of sensors that can be added make it suitable for many applications, including:
The ORAKEL controller can be connected to up to 16 sensors for an application. The following flow and quality sensors are available:
Inputs
2 configurable sensor inputs; 4-20mA loop powered, 0-2 VDC, +/- 1200 mV for pH, ORP, or ISEs, PT100, pulse and Modbus. Unused inputs can be used as Outputs. Up to 8 digital inputs.
Dimensions
230 x 309 x 103mm.
Alarms
2 user configurable alarms with deadband and delay for each parameter and control output.
Thresholds
2 user configurable thresholds (for control) with deadband and delay for each measurement and control output.
PID
Configurable flow proportional PID – multiple loops.
Communication (Optional)
Modbus ASCII/RTU (RS485).
Profibus DP.
Modbus TCP (Ethernet) 2G/3G modem.
Data Logging
Internal – single parameter data log or status message log over 1 million records (downloadable data logs optional).
Outputs
2 configurable analogue outputs; 0-20mA, 4-20mA, 0-1 VDC, 0-10 VDC, 1-10 VDC.
Up to 8 SPST electromechanical relays rated 380 VAC, 6A maximum (relays are rated 6A for resistive loads and 2A for inductive loads).
Languages
Any non-pictogram by request.
Any Latin, Cyrillic, Hellenic.
Memory Backup
All user configuration is stored in non-volatile on-board flash memory.
Enclosure
ABS flame retardant IP65N, Nema 4X.
Display
4.3″, 480 x 272, 8 bit, greyscale
(4.3″, 480 x 272, full colour optional).
Weight
2kg.
Warranty
12 months from date of purchase.
The ORAKEL Suspended Solids senor has a large dynamic range, which eliminates the need for a “zero” and also eliminates the effect of background light.
For multiple measuring ranges, the suspended solids sensor can monitor turbidity and suspended solids from 2 NTU (1mg/l) to 8%* solids.
The ORAKEL range of Conductivity meters also double as a Salinity meter and a TDS meter. The range measures conductivity in water from 0 to 2,000,000 µS/cm (range selectable). You can choose between a standard graphite sensor and a more sophisticated toroidal sensor, or stainless steel ‘special’ sensors for high temperature, high pressure conductivity measurement applications.
The ORAKEL peracetic acid sensor is a membrane device which use no reagents. It is extremely stable and has a reduced maintenance and reduced whole life costs.
With its reduced maintenance, reduced calibration and reduced spares requirements, the ORAKEL peracetic acid sensor is arguably the most cost effective peracetic acid analyser available.
Particle counters are known for their ability to detect when a filter is reaching the end of its life. ORAKEL Particle Counters are sophisticated instruments suitable for municipal and industrial water treatment applications including filter performance monitoring, protecting RO membranes from colloidal fouling and corrosion product monitoring.
The pH5 electrode has a double-junction reference to prevent contamination of the reference from sample components.
This design gives the electrode a longer life compared to ordinary electrodes (up to 3 yrs). The electrode also has a hemi-shaped glass measuring surface which is more durable than the traditional bulb-shaped glass.
Sitting at the top end of the market place, the ORAKEL pH probe has a longer life and lower maintenance requirements. Typically it only needs calibrating once every two or three months, making it a very cost effective solution.
The ORAKEL Turbidity monitor automatically varies the light output so that the turbidity can be measured independently of background light and electronic drift. It is ISO 7027 compliant and covers a range of 0.01-1000 NTU (0.01-2000mg/l depending on the sample).
The ORAKEL System determines true turbidity and/or suspended solids in water, using a nephelometric measurement of scattered light in accordance with ISO 7027. The sensor uses lifetime-based optical technology to provide an extremely stable, accurate, low maintenance sensor with no moving parts and no consumables.